11-H3kVA Standart Çevrimiçi Çift Dönüşümlü UPS – 3000VA/2700W Güç Koruması

The 11-H3kVA Standard Model is a high-performance 3kVA online double-conversion UPS featuring DSP technology, a 0.9 output power factor, and a wide input voltage range (90V-300V). Ideal for government, telecom, and medical applications. Includes smart battery management and optional SNMP monitoring.

Fiyat Teklifi Alın ve Teknik Destek Alın

Başvurunuzu, talep ettiğiniz miktarı ve teknik gereksinimlerinizi bize iletin. Mühendislik ekibimiz size uygun bir konfigürasyon önerisiyle yanıt verecektir.

Açıklama

11-H3kVA (Standard Model)

I. Power Range: 3kVA

Çalışma Modu: Single-phase input / Single-phase output, Online Double-Conversion.
Kullanım alanları: Widely used across various sectors including government, finance, telecommunications, education, transportation, meteorology, broadcasting, taxation, healthcare, energy, and power industries.

Ürün Özellikleri:

  • Gerçek Çevrimiçi Çift Dönüştürme: Provides continuous, high-quality power by isolating the load from utility irregularities.

  • Mikroişlemci Kontrolü: Ensures high reliability and precise operation through advanced digital management.

  • Giriş Güç Faktörü Düzeltmesi: Optimizes energy usage and reduces harmonic distortion on the grid.

  • Yüksek Çıkış Güç Katsayısı: Output Power Factor reaches up to 0.9, providing more real power for connected loads.

  • Wide Input Voltage Range (90V – 300V): Capable of operating in unstable power environments without switching to battery mode.

  • Verimli Frekans Dönüştürücü Modu: Supports conversion between 50Hz and 60Hz to meet specialized equipment needs.

  • Jeneratörle Uyumlu: Yedek jeneratör sistemleriyle sorunsuz bir şekilde çalışır.

  • Enhanced Monitoring Options: Optional SNMP card allows for standalone monitoring or integrated management via USB and RS232 ports.

  • User-Friendly LCD Display: Offers simple operation and comprehensive, real-time monitoring of UPS status.

  • ECO Modu: Provides high-efficiency energy-saving operation to reduce electricity costs.

  • Acil Durum Güç Kapatma (EPO): Allows for immediate shutdown in the event of an emergency.

  • DSP Technology: Built on advanced Digital Signal Processing technology; optional maintenance bypass switch available.

  • Smart Battery Charger Design: Optimizes battery performance and significantly extends battery lifespan.

  • İzolasyon Transformatörü: Optional built-in isolation transformer for enhanced electrical protection.

II. Technical Notes:

Ürün11-H1kVA11-H2kVA11-H3kVA11-H6kVA11-H10 kVA
Model11-H1kVA11-H2kVA11-H3kVA11-H6kVA11-H10 kVA
Kapasite1000 VA/900 W2000 VA/1800 W3000 VA/2700 W6000 VA/5400 W10.000 VA/9.000 W
### Input
AşamaSingle-phase groundedSingle-phase groundedSingle-phase groundedSingle-phase groundedSingle-phase grounded
Minimum Transfer Voltagecolspan=”3″160VAC/140VAC/120VAC/110VAC ±5% (Ambient temp <35℃; Load Ratio: 100%-80%-80%-70%-70%-70%-60%-60%-0)colspan=”2″50% Load: 110VAC ±3%;

100% Load: 176VAC ±3%

Minimum Restore Voltagecolspan=”3″195VAC/175VAC/155VAC/135VAC ±5% (Ambient temp <35℃; Load Ratio: 100%-80%-80%-70%-70%-60%-60%-0)colspan=”2″Minimum transfer voltage +10V
Maximum Transfer Voltagecolspan=”3″300 VAC ±51 TP3Tcolspan=”2″300 VAC ±31 TP3T
Maximum Restore Voltagecolspan=”3″290 VAC ±51 TP3Tcolspan=”2″Maximum transfer voltage -10V
Frekans Aralığıcolspan=”3″40Hz ~ 70Hzcolspan=”2″46Hz~54Hz (@50Hz System);

56Hz~64Hz (@60Hz System)

Giriş Güç Faktörücolspan=”3″≥0.99 @ 220-230-240VACcolspan=”2″Yok
### Output
Çıkış Gerilimicolspan=”3″208/220/230/240VAC ±1%colspan=”2″208/220/230/240VAC ±1%
Frequency Range (Synchronization)colspan=”3″47-53 Hz veya 57-63 Hzcolspan=”2″46–54 Hz veya 56–64 Hz
Frekans Aralığı (Pil Modu)colspan=”3″50±0.25Hz or 60±0.3Hzcolspan=”2″50±0.1Hz or 60±0.1Hz
Tepe Faktörücolspan=”5″3:1
Total Harmonic Distortion (THD)colspan=”3″≤3% THD (Linear Load); ≤6% THD (Non-linear Load)colspan=”2″≤3% THD (Linear Load); ≤5% THD (Non-linear Load)
Aşırı Yük Kapasitesicolspan=”3″Temp<35℃:

105%-110%: Auto-restart after 10s fault, recover output within 1s when input normalizes

110%-130%: Auto-shutdown after 3 mins, recover after 3s when input normalizes

>150%: Instant UPS shutdown

colspan=”2″100%~110%: 30 Minutes

110%~130%: 5 Minutes

>130%: 10 Seconds

Transfer Time (Mains to Battery)colspan=”3″0 mscolspan=”2″0 ms
Transfer Time (Inverter to Bypass)colspan=”3″4ms (Standard Condition)colspan=”2″0 ms
Dalga Şekli (Pil Modu)colspan=”3″Saf Sinüs Dalgasıcolspan=”2″Yok
### Efficiency
Şebeke Modu88%89%90%92%93%
Pil Modu83%87%88%90%91%
### Battery
Standard Unit (S)
Pil Türücolspan=”3″12 V/7 Ahcolspan=”2″12 V/7 Ah
Pil Adedi2461216
Şarj Akımıcolspan=”3″1,0 Acolspan=”2″Preset: 1.0A ±10%, Max: 1A/2A
Long-run Unit (L)
Pil Türücolspan=”5″12V/AH (Customized per buyer request)
Pil Adedi338colspan=”2″Model-dependent
Şarj Akımıcolspan=”3″1A/2A/4A/6Acolspan=”2″1A/2A/4A/6A (Adjustable);

6A only applicable for 16-cell battery pack

### Physical Specifications
Standard Unit
Dimension (D×W×H, mm)282×145×220397×145×220421×190×318369×190×688442×190×688
Net Ağırlık (kg)9.81726.25155
Long-run Unit
Dimension (D×W×H, mm)282×145×220397×145×220421×190×318369×190×318442×190×318
Net Ağırlık (kg)4.46.87.41215
### Operating Environment
Çalışma Nemicolspan=”3″20-90% RH, 0-40℃ (Non-condensing)colspan=”2″<95% RH, Non-condensing
Gürültücolspan=”3″<50dB @ 1 Meter<55dB @ 1 Meter<58dB @ 1 Meter
Çalışma Sıcaklığıcolspan=”3″Yokcolspan=”2″0 ~ 40℃ (Battery lifespan shortened above 25℃ ambient temp)
### Control & Management
Intelligent RS-232/USBcolspan=”5″Compatible with Windows 2000/2003/XP/Vista/2008, Windows7/8, Linux & MAC
İsteğe Bağlı SNMP Kartıcolspan=”5″Supports SNMP network management & remote monitoring

 

  • Derating Rules for 1-3kVA Models: Output power will be derated to 80% of capacity when the UPS is set to CVCF (Constant Voltage Constant Frequency) mode or when the output voltage is configured to 208VAC.

  • Derating Rules for 6/10kVA Models: Output power will be derated to 60% in CVCF mode and to 90% when the output voltage is set to 208VAC.

  • Paralel Yedeklilik: The standard models listed above currently do not support parallel redundancy.

  • Gerilim Desteği: Output voltage settings of 200/208/220/230/240VAC are only applicable to Long-run (L) models.

  • For 1-3kVA UPS: The output power is derated to 80% when operating in CVCF (Constant Voltage Constant Frequency) mode or when the output voltage is set to 208VAC.

  • For 6/10kVA UPS: The output power is derated to 60% in CVCF mode and to 90% when the output voltage is set to 208VAC.

  • The standard models mentioned above currently do not support parallel redundancy.

  • The voltage settings of 200/208/220/230/240VAC are only applicable to long-run models.
    11-H3kVA Standard Online Double-Conversion UPS - 3000VA/2700W Power Protection technical detail 1 by DAXIN ENERGY

Yorumlar

Henüz herhangi bir yorum yok.

“11-H3kVA Standard Online Double-Conversion UPS – 3000VA/2700W Power Protection” için ilk yorum yazan siz olun”

E-posta adresiniz yayınlanmayacak. Gerekli alanlar * ile işaretlenmişlerdir