11-H 6kVA Online UPS Long Backup Model | External Battery Uninterruptible Power Supply

Description

The 11-H 6kVA Long Backup Online UPS adopts advanced double-conversion technology to provide continuous, stable, and clean power for critical equipment. It supports external battery packs for extended backup time, making it ideal for applications requiring long-duration power protection.
Applications:
Widely used in government, finance, telecommunications, education, transportation, meteorology, broadcasting, taxation, healthcare, and energy sectors. Especially suitable for critical applications requiring extended backup time.
Notes:

  • In frequency conversion mode:
    • 1–3kVA models derate to 80% output
    • 6/10kVA models derate to 60% output
  • At 208VAC output:
    • 1–3kVA derate to 80%
    • 6/10kVA derate to 90%
  • Parallel redundancy is not supported
  • 200/208/220/230/240VAC applies only to long backup models
    Parameter 11-H1kVA 11-H2kVA 11-H3kVA 11-H6kVA 11-H10kVA
    Model 11-H1kVA 11-H2kVA 11-H3kVA 11-H6kVA 11-H10kVA
    Capacity 1000VA/900W 2000VA/1800W 3000VA/2700W 6000VA/5400W 10000VA/9000W
    Input
    Phase \multicolumn{3}{c}{Single-phase, grounded} \multicolumn{2}{c}{Single-phase, grounded}
    Voltage Range
    Lowest Transfer Voltage \multicolumn{3}{c}{160/140/120/110VAC ±5% (Ambient temp <35°C)

    (Adjustable with load ratio: 100%-80% / 80%-70% / 70%-60% / 60%-0)}

    \multicolumn{2}{c}{50% load: 110VAC ±3%

    100% load: 176VAC ±3%}

    Lowest Restore Voltage \multicolumn{3}{c}{195/175/155/135VAC ±5% (Ambient temp <35°C)

    (Adjustable with load ratio: 100%-80% / 80%-70% / 70%-60% / 60%-0)}

    \multicolumn{2}{c}{Lowest transfer voltage +10V}
    Highest Transfer Voltage \multicolumn{3}{c}{300VAC ±5%} \multicolumn{2}{c}{300VAC ±3%}
    Highest Restore Voltage \multicolumn{3}{c}{290VAC ±5%} \multicolumn{2}{c}{Highest transfer voltage -10V}
    Frequency Range \multicolumn{3}{c}{40Hz ~ 70Hz} \multicolumn{2}{c}{46Hz~54Hz @ 50Hz system; 56Hz~64Hz @ 60Hz system}
    Power Factor \multicolumn{3}{c}{≥0.99 @ 220-230VAC (input voltage)} \multicolumn{2}{c}{—}
    Output
    Output Voltage \multicolumn{5}{c}{208/220/230/240VAC ±1%}
    Mains Voltage Range (Battery Mode) \multicolumn{5}{c}{±1%}
    Frequency Range (Synchronization Range) \multicolumn{3}{c}{47-53Hz or 57-63Hz} \multicolumn{2}{c}{46-54Hz or 56-64Hz}
    Frequency Range (Battery Mode) \multicolumn{3}{c}{50±0.25Hz or 60±0.3Hz} \multicolumn{2}{c}{50±0.1Hz or 60±0.1Hz}
    Crest Factor \multicolumn{5}{c}{3:1}
    Harmonic Distortion \multicolumn{3}{c}{≤3% THD (linear load); ≤6% THD (non-linear load)} \multicolumn{2}{c}{≤3% THD (linear load); ≤5% THD (non-linear load)}
    Overload Capacity \multicolumn{3}{c}{Ambient temp <35°C: 105%-110%: UPS shuts down after 10s in battery mode, transfers to bypass on mains restore. 110%-130%: UPS shuts down after 3s in battery mode, transfers to bypass on mains restore. >150%: UPS shuts down immediately.} \multicolumn{2}{c}{100%-110%: 30 minutes; 110%-130%: 5 minutes; >130%: 10 seconds}
    Transfer Time
    Mains to Battery \multicolumn{5}{c}{0ms}
    Inverter to Bypass \multicolumn{3}{c}{4ms (standard conditions)} \multicolumn{2}{c}{0ms}
    Waveform (Battery Mode) \multicolumn{3}{c}{Pure sine wave} \multicolumn{2}{c}{—}
    Efficiency
    Mains Mode 88% 89% 90% 92% 93%
    Battery Mode 83% 87% 88% 90% 91%
    Battery
    Standard Model (S)
    Battery Type \multicolumn{3}{c}{12V/7Ah} \multicolumn{2}{c}{12V/7Ah}
    Quantity 2 4 6 12 16
    Charging Current 1.0A \multicolumn{2}{c}{Preset: 1.0A ±10%, Max: 1A/2A}
    Long Backup Model (L)
    Battery Type \multicolumn{5}{c}{12V/AH (depends on customer selection)}
    Quantity 3 6 8 16 16
    Charging Current 1A/2A/4A/6A 1A/2A/4A/6A 1A/2A/4A/6A 1A/2A/4A/6A (adjustable; 6A only for 16-cell batteries) 1A/2A/4A/6A (adjustable; 6A only for 16-cell batteries)
    Physical Specifications
    Standard Model
    Dimensions: D×W×H (mm) 282×145×220 397×145×220 421×190×318 369×190×688 442×190×688
    Net Weight (kg) 9.8 17 26.2 51 55
    Long Backup Model
    Dimensions: D×W×H (mm) 282×145×220 397×145×220 421×190×318 369×190×318 442×190×318
    Net Weight (kg) 4.4 6.8 7.4 12 15
    Operating Environment
    Humidity \multicolumn{3}{c}{20-90% RH, 0-40°C (non-condensing)} \multicolumn{2}{c}{<95% RH, non-condensing}
    Noise Level <50dB @ 1m <50dB @ 1m <50dB @ 1m <55dB @ 1m <58dB @ 1m
    Temperature \multicolumn{3}{c}{—} \multicolumn{2}{c}{0~40°C (battery life shortened above 25°C)}
    Control & Management
    Smart RS-232/USB \multicolumn{5}{c}{Supports Windows 2000/2003/XP/Vista/2008, Windows 7/8, Linux, and MAC}
    Optional SNMP Card \multicolumn{5}{c}{Supports SNMP and network management}

Footnotes

  1. Output power is reduced to 80% in frequency conversion mode, or when the output voltage is set to 208VAC.
  2. Specifications are subject to change without prior notice.

Reviews

There are no reviews yet.

Be the first to review “11-H 6kVA Online UPS Long Backup Model | External Battery Uninterruptible Power Supply”

Your email address will not be published. Required fields are marked *