الوصف
What Is the DAXIN RM33 180kVA Modular Online UPS?
The DAXIN RM33 180kVA is a three-phase modular online UPS system designed for scalable critical-power protection in data centers, telecom facilities, industrial plants and other mission-critical applications.
Its modular cabinet architecture integrates power modules, centralized control, protection and service access within a scalable UPS platform, allowing installed capacity and redundancy to be configured according to project requirements.
تدعم سلسلة RM33 مدخلات ومخرجات ثلاثية الطور بقيم 3 × 380/400/415 فولت تيار متردد، وعامل قدرة مدخلات لا يقل عن 0.99 عند الحمل الكامل، ومؤشر التشوه التوافقي الكلي (THDi) للتيار المدخل أقل من 2%، وكفاءة نظام تصل إلى 96.5%.
Battery configuration, backup runtime, redundancy architecture, communications and project accessories should be confirmed according to the connected load and approved DAXIN technical proposal.
DAXIN RM33-180kVA Key Specifications
| المعلمة | المواصفات |
|---|---|
| الطراز | RM33-180kVA |
| نوع UPS | وحدة تزويد الطاقة غير المنقطعة (UPS) المعيارية عبر الإنترنت |
| المرحلة | مدخل ثلاثي الأطوار / مخرج ثلاثي الأطوار |
| سعة الخزانة | 180kW or 120kW configuration |
| نوع البطارية | حزمة بطارية خارجية |
| سعة خزانة البطاريات | 30 كيلو فولت أمبير / 30 كيلوواط |
| خزانات البطاريات الاختيارية | Up to 6 |
| جهد الدخل | 3 × 380/400/415 فولت تيار متردد (ثلاثي الأطوار + N) |
| تردد الإدخال | 50/60 هرتز، الكشف التلقائي |
| نطاق تردد الإدخال | 40–70 هرتز |
| معامل القدرة الكهربائية المدخلة | ≥0.99 عند حمل 100% |
| التشويه التوافقي الكلي لتيار الدخل (THDi) | <2% @ 100% الحمل |
| جهد الخرج | 3 × 380/400/415 فولت تيار متردد (ثلاثي الأطوار + N) |
| استقرار الجهد الساكن | ≤±0.3% الحمل النموذجي |
| استقرار الجهد الديناميكي | ≤±3% الحمولة النموذجية |
| تردد الخرج | 50/60 هرتز |
| نطاق التردد | 46–54Hz or 56–64Hz |
| التشويه التوافقي الكلي (THD) في الخرج | ≤1% خطي / ≤2% غير خطي |
| الكفاءة | ما يصل إلى 96.5% |
| الأبعاد | 1100 × 600 × 1475mm |
| الوزن الصافي | 195 / 223kg |
| درجة حرارة التشغيل | 0–40 درجة مئوية |
| الارتفاع | <1000m at Rated Power |
| مستوى الحماية | IP20 |
| التواصل | RS-232 / USB |
| إدارة الشبكة | SNMP اختياري |
المزايا الرئيسية
- 180kVA Modular UPS Platform: Designed for scalable three-phase critical-power applications in data centers, telecom and industrial facilities.
- بنية معيارية قابلة للتوسع: Power-module configuration can be planned according to current load, redundancy requirements and future expansion.
- حماية التيار الكهربائي ثلاثي الأطوار: Supports 3 × 380/400/415VAC three-phase input and output.
- انخفاض تشوه التوافقي في الإدخال: يساعد معدل التشوه التوافقي الكلي (THDi) لتيار الإدخال الذي يقل عن 2% عند الحمل الكامل على تقليل التأثير الكهربائي على الشبكة.
- معامل قدرة مدخلات عالي: يبلغ معامل القدرة عند الدخل 0.99 على الأقل عند حمل 100%.
- كفاءة عالية: تبلغ كفاءة النظام ما يصل إلى 96.51 TP3T.
- إعدادات البطارية الخارجية: Battery capacity and backup runtime can be engineered according to project requirements.
- المراقبة عن بُعد: يتم دعم الاتصال عبر RS-232/USB، مع إمكانية إدارة الشبكة عبر بروتوكول SNMP بشكل اختياري.
ما هو نظام UPS المعياري؟
A modular UPS system uses multiple power modules within a common UPS cabinet instead of relying on a single fixed-capacity power stage.
This architecture allows capacity, redundancy and maintenance strategy to be planned according to the critical load, required availability and future expansion.
The DAXIN RM33 series combines modular power architecture, centralized control, external battery configurations and network-management options for scalable critical-power applications.
How Should an 180kVA Modular UPS Be Sized?
An 180kVA modular UPS should be sized according to the actual critical load in kW and kVA, load power factor, required redundancy, expected future expansion and battery autonomy.
Modular system design should also consider the number and rating of installed power modules, bypass architecture, upstream and downstream protection, communication requirements and maintenance strategy.
DAXIN ENERGY can review the load list, single-line diagram, required backup time and redundancy target before confirming the final RM33 system configuration.
معلومات عن المنتج والمراجع الفنية

التطبيقات النموذجية
- مراكز البيانات وغرف الخوادم
- المرافق الأساسية للاتصالات والبنية التحتية للشبكة
- الأتمتة الصناعية ومصانع الإنتاج
- الخدمات المالية والمصرفية
- الرعاية الصحية والبنية التحتية الطبية
- النقل والبنية التحتية العامة
- مرافق تكنولوجيا المعلومات المؤسسية
- أنظمة طاقة أخرى قابلة للتوسع وذات أهمية حاسمة لأداء المهام
الاختيار وتخطيط المشاريع
يرجى التأكد من القوة الكهربائية الدقيقة، وطور الدخل/الخرج، والجهد، والتردد، ومعامل القدرة، وجهد البطارية، ومدة التشغيل، ونظام التجاوز، ووسائل الاتصال، والأبعاد، والحدود البيئية، وطريقة التركيب، مقارنةً بالطراز المختار ورسومات المشروع قبل تقديم الطلب.
الأسئلة الشائعة
هل يمكن تخصيص هذا المنتج لمشروع معين؟
نعم. يمكن مراجعة التكوين الكهربائي، ومدة تشغيل البطارية، وأنظمة الاتصالات، ونظام التجاوز، وترتيب الخزانات، وملحقات المشروع، وفقًا لمتطلبات الموقع.
هل يتم تطبيق جميع التصنيفات الفنية على السلسلة بأكملها؟
لا. تختلف القيم التصنيفية والوظائف باختلاف الطراز والتكوين. يرجى الاعتماد على ورقة المواصفات الفنية الخاصة بالمشروع كمرجع نهائي.
هل يمكن لشركة «داكسين إنيرجي» تقديم الدعم في اختيار النظام؟
نعم. يرجى تقديم قائمة الأحمال، وبيانات الطور والجهد الكهربائي، ومدة التشغيل المطلوبة، والهدف المحدد للتكرار، ومتطلبات الاتصال، وبيئة التركيب.
طلب تكوين مشروع
يرجى إرسال بيانات الحمل، والرسم التخطيطي أحادي الخط، ووقت النسخ الاحتياطي المطلوب، وظروف الموقع للحصول على عرض مخصص لجهاز UPS أو البطاريات.
What is the DAXIN RM33 180kVA?
The DAXIN RM33 180kVA is a three-phase modular online UPS system designed for scalable critical-power applications.
ما هي قيم جهد الدخل والخروج التي يدعمها هذا الجهاز؟
تُدرج المواصفات المرجعية مدخلات ومخرجات ثلاثية الأطوار بقدرة 3 × 380/400/415 فولت تيار متردد.
ما هو معامل القدرة الكهربائية المدخلة ومؤشر التهيدروليكية الكلية (THDi)؟
The RM33 reference specification lists an input power factor of at least 0.99 at full load and input current THDi below 2%.
What is the efficiency of the RM33 modular UPS?
The reference specification lists system efficiency up to 96.5%. Actual efficiency depends on load and system configuration.
هل يدعم جهاز RM33 المراقبة عن بُعد؟
Yes. RS-232/USB communication is supported, with optional SNMP network management.
Can the RM33-180kVA system be configured for redundancy?
Yes, modular architecture allows redundancy requirements to be considered during system design. Final module quantity, redundancy architecture and installed capacity should be confirmed in the approved technical proposal.









المراجعات
لا توجد مراجعات بعد.