Description
3H30kVA High-Frequency Online UPS for Industrial Backup Power
The DAXIN ENERGY 3H30kVA high-frequency online UPS is engineered for
high-demand backup power applications that require stable, reliable and
continuous power protection. It is suitable for data centers, telecom power
rooms, industrial automation systems, commercial buildings, security systems
and other mission-critical electrical equipment.
Onduleur à double conversion en ligne « True »
The 3H30kVA online UPS adopts true online double-conversion technology to
isolate connected loads from unstable grid power, voltage fluctuation,
frequency variation, transient interference and power interruptions. It
provides clean and stable output power for sensitive equipment.
High Reliability Design
- 30kVA / 24kW rated capacity for medium and large backup power systems
- True online double-conversion UPS architecture
- MCU + DSP digital control for accurate and stable operation
- Generator input compatible, recommended generator capacity is 2 times UPS capacity
- Optional output isolation transformer can be installed before shipment
- Fonction d'arrêt d'urgence standard EPO
- Supports parallel operation up to 3 units for compatible models
- Battery quantity can be configured from 18 to 20 pcs according to site requirements
- 12A ±10% charging current for 30kVA configuration
- Available with PF0.8 and PF0.9 power factor versions
- Supports automatic startup after mains power recovery
Comprehensive Protection Functions
The UPS integrates multiple protection functions, including output overload
protection, output short-circuit protection, inverter over-temperature
protection, low battery warning and battery overcharge protection. These
functions help improve system reliability, reduce downtime and protect
connected critical equipment.
Maintenance Bypass for Easier Service
An optional manual maintenance bypass switch can be configured. When UPS
maintenance or fault inspection is required, the load can be transferred to
bypass power without interruption, making maintenance safer, faster and more
convenient.
LCD Display and Remote Monitoring
The LCD display provides real-time UPS operating status, input voltage,
output voltage, frequency, battery information and alarm status. RS232 / USB
communication and optional SNMP network monitoring allow users to manage UPS
operation through intelligent monitoring software.
Adaptable for Demanding Environments
The circuit boards are installed in an enclosed structure and treated with
protective conformal coating, improving environmental adaptability for
industrial sites, tunnels, plazas, telecom rooms and other demanding
installation environments.
Applications typiques
- Centres de données et salles de serveurs
- Telecom power rooms and communication stations
- Industrial automation and control systems
- Commercial buildings and office facilities
- Security, monitoring and access control systems
- Medical, transportation and public infrastructure backup power
Technical Specifications – 3H30kVA Online UPS
| Modèle | 3 h 30 kVA |
|---|---|
| Capacité | 30 kVA / 24 kW |
| Phase d'entrée | Triphasé à trois fils |
| Plage de tension d'entrée | 110VAC ±3% at 50% load; 176VAC ±3% at 100% load; maximum 300VAC ±3% |
| Plage de fréquences d'entrée | 46-54Hz at 50Hz system; 56-64Hz at 60Hz system |
| Facteur de puissance d'entrée | ≥0.99 at 100% load |
| Tension de sortie | 208 / 220 / 230 / 240 V CA |
| Régulation de la tension alternative | ±1% |
| Fréquence en mode batterie | 50 Hz ± 0,1 Hz ou 60 Hz ± 0,1 Hz |
| Ratio de crête actuel | 3:1 max. |
| Distorsion harmonique | ≤2% THD linear load; ≤5% THD non-linear load |
| Durée du transfert | 0ms from mains to battery; 0ms from inverter to bypass |
| Capacité de surcharge | 100%-110%: 10 min; 110%-130%: 1 min; >130%: 1 sec |
| Efficacité | >90% in AC mode; >88% in battery mode |
| Type de batterie | Sealed lead-acid battery |
| Nombre de piles | 18-20 pcs configurable |
| Courant de charge | 12A ±10% |
| Dimensions | 910 × 380 × 910 mm |
| Poids net | 67,3 kg |
| Température de fonctionnement | 0-40°C; battery life may be shortened above 25°C |
| Humidité relative | <95%, sans condensation |
| Altitude de fonctionnement | < 1 000 m |
| Niveau sonore | <65dB at 1 meter |
| Interface de communication | RS232 / USB, supports Windows, Linux, Unix and Mac systems |
| SNMP (en option) | SNMP network monitoring and power management support |
FAQ – 3H30kVA High-Frequency Online UPS
What is the rated capacity of the DAXIN ENERGY 3H30kVA online UPS?
The DAXIN ENERGY 3H30kVA online UPS has a rated capacity of 30kVA / 24kW, making it suitable for industrial, telecom, data center and commercial backup power applications.
What type of UPS technology does the 3H30kVA model use?
The 3H30kVA model uses true online double-conversion technology to provide stable output power and protect connected loads from voltage fluctuation, frequency variation and power interruptions.
What applications is the 3H30kVA high-frequency online UPS suitable for?
It is suitable for data centers, telecom power rooms, industrial automation systems, commercial buildings, security systems, monitoring systems and other critical power protection applications.
Does the 3H30kVA online UPS support generator input?
Yes. The UPS is compatible with generator input. For stable operation, the recommended generator capacity is 2 times the UPS capacity.
Does the UPS support remote monitoring?
Yes. The UPS supports RS232 / USB communication and optional SNMP network monitoring, allowing users to monitor UPS status, battery information and alarms through intelligent UPS management software.
What is the transfer time of this online UPS?
The transfer time is 0ms from mains power to battery mode and 0ms from inverter to bypass, helping ensure continuous power for critical loads.
What battery configuration does the 3H30kVA UPS use?
The 3H30kVA UPS uses sealed lead-acid batteries, with 18-20 batteries configurable according to site requirements.
What protection functions are included?
The UPS includes output overload protection, output short-circuit protection, inverter over-temperature protection, low battery warning and battery overcharge protection.









Avis