Description

The 11-H 6kVA Long Backup Online UPS adopts advanced double-conversion technology to provide continuous, stable, and clean power for critical equipment. It supports external battery packs for extended backup time, making it ideal for applications requiring long-duration power protection.
Applications:
Widely used in government, finance, telecommunications, education, transportation, meteorology, broadcasting, taxation, healthcare, and energy sectors. Especially suitable for critical applications requiring extended backup time.
Notes:

  • In frequency conversion mode:
    • 1–3kVA models derate to 80% output
    • 6/10kVA models derate to 60% output
  • At 208VAC output:
    • 1–3kVA derate to 80%
    • 6/10kVA derate to 90%
  • Parallel redundancy is not supported
  • 200/208/220/230/240VAC applies only to long backup models
    Parameter 11-H1kVA 11-H2kVA 11-H3kVA 11-H6kVA 11-H10kVA
    Model 11-H1kVA 11-H2kVA 11-H3kVA 11-H6kVA 11-H10kVA
    Capacity 1000VA/900W 2000VA/1800W 3000VA/2700W 6000VA/5400W 10000VA/9000W
    Input
    Phase \multicolumn{3}{c}{Single-phase, grounded} \multicolumn{2}{c}{Single-phase, grounded}
    Voltage Range
    Lowest Transfer Voltage \multicolumn{3}{c}{160/140/120/110VAC ±5% (Ambient temp <35°C)

    (Adjustable with load ratio: 100%-80% / 80%-70% / 70%-60% / 60%-0)}

    \multicolumn{2}{c}{50% load: 110VAC ±3%

    100% load: 176VAC ±3%}

    Lowest Restore Voltage \multicolumn{3}{c}{195/175/155/135VAC ±5% (Ambient temp <35°C)

    (Adjustable with load ratio: 100%-80% / 80%-70% / 70%-60% / 60%-0)}

    \multicolumn{2}{c}{Lowest transfer voltage +10V}
    Highest Transfer Voltage \multicolumn{3}{c}{300VAC ±5%} \multicolumn{2}{c}{300VAC ±3%}
    Highest Restore Voltage \multicolumn{3}{c}{290VAC ±5%} \multicolumn{2}{c}{Highest transfer voltage -10V}
    Frequency Range \multicolumn{3}{c}{40Hz ~ 70Hz} \multicolumn{2}{c}{46Hz~54Hz @ 50Hz system; 56Hz~64Hz @ 60Hz system}
    Power Factor \multicolumn{3}{c}{≥0.99 @ 220-230VAC (input voltage)} \multicolumn{2}{c}{—}
    Output
    Output Voltage \multicolumn{5}{c}{208/220/230/240VAC ±1%}
    Mains Voltage Range (Battery Mode) \multicolumn{5}{c}{±1%}
    Frequency Range (Synchronization Range) \multicolumn{3}{c}{47-53Hz or 57-63Hz} \multicolumn{2}{c}{46-54Hz or 56-64Hz}
    Frequency Range (Battery Mode) \multicolumn{3}{c}{50±0.25Hz or 60±0.3Hz} \multicolumn{2}{c}{50±0.1Hz or 60±0.1Hz}
    Crest Factor \multicolumn{5}{c}{3:1}
    Harmonic Distortion \multicolumn{3}{c}{≤3% THD (linear load); ≤6% THD (non-linear load)} \multicolumn{2}{c}{≤3% THD (linear load); ≤5% THD (non-linear load)}
    Overload Capacity \multicolumn{3}{c}{Ambient temp <35°C: 105%-110%: UPS shuts down after 10s in battery mode, transfers to bypass on mains restore. 110%-130%: UPS shuts down after 3s in battery mode, transfers to bypass on mains restore. >150%: UPS shuts down immediately.} \multicolumn{2}{c}{100%-110%: 30 minutes; 110%-130%: 5 minutes; >130%: 10 seconds}
    Transfer Time
    Mains to Battery \multicolumn{5}{c}{0ms}
    Inverter to Bypass \multicolumn{3}{c}{4ms (standard conditions)} \multicolumn{2}{c}{0ms}
    Waveform (Battery Mode) \multicolumn{3}{c}{Pure sine wave} \multicolumn{2}{c}{—}
    Efficiency
    Mains Mode 88% 89% 90% 92% 93%
    Battery Mode 83% 87% 88% 90% 91%
    Battery
    Standard Model (S)
    Battery Type \multicolumn{3}{c}{12V/7Ah} \multicolumn{2}{c}{12V/7Ah}
    Quantity 2 4 6 12 16
    Charging Current 1.0A \multicolumn{2}{c}{Preset: 1.0A ±10%, Max: 1A/2A}
    Long Backup Model (L)
    Battery Type \multicolumn{5}{c}{12V/AH (depends on customer selection)}
    Quantity 3 6 8 16 16
    Charging Current 1A/2A/4A/6A 1A/2A/4A/6A 1A/2A/4A/6A 1A/2A/4A/6A (adjustable; 6A only for 16-cell batteries) 1A/2A/4A/6A (adjustable; 6A only for 16-cell batteries)
    Physical Specifications
    Standard Model
    Dimensions: D×W×H (mm) 282×145×220 397×145×220 421×190×318 369×190×688 442×190×688
    Net Weight (kg) 9.8 17 26.2 51 55
    Long Backup Model
    Dimensions: D×W×H (mm) 282×145×220 397×145×220 421×190×318 369×190×318 442×190×318
    Net Weight (kg) 4.4 6.8 7.4 12 15
    Operating Environment
    Humidity \multicolumn{3}{c}{20-90% RH, 0-40°C (non-condensing)} \multicolumn{2}{c}{<95% RH, non-condensing}
    Noise Level <50dB @ 1m <50dB @ 1m <50dB @ 1m <55dB @ 1m <58dB @ 1m
    Temperature \multicolumn{3}{c}{—} \multicolumn{2}{c}{0~40°C (battery life shortened above 25°C)}
    Control & Management
    Smart RS-232/USB \multicolumn{5}{c}{Supports Windows 2000/2003/XP/Vista/2008, Windows 7/8, Linux, and MAC}
    Optional SNMP Card \multicolumn{5}{c}{Supports SNMP and network management}

Footnotes

  1. Output power is reduced to 80% in frequency conversion mode, or when the output voltage is set to 208VAC.
  2. Specifications are subject to change without prior notice.